(9)web.jpg)
· Easy to use
· Compact, rugged enclosure
· Simple push button test action
· Test Class I and II equipment including IT and business equipment
· Differential Leakage test
· Extension cord and IEC lead tests
· Power socket polarity
· LCD display giving clear pass/fail indication
· Supplied with test lead, IEC lead, instruction manual and deluxe carring case with shoulder strap
A 10 second test sequence quickly confirms the integrity of:
1. ground continuity
2. insulation resistance (dielectric)
3. Class 1 current leakage
4. Class II current leakage
5. Wiring polarity of the both the device and the power source
Ground Continuity
Test Current - 10A rms nominal
Test Duration - 2s nominal
Measurement Accuracy - 5%
Pass Value - 0.2 W
Insulation Resistance
Test Voltage - 500V DC
Test Voltage Accuracy - +20%, -0%
Test Current - 1mA into 500kW
< 2mA short circuit
Measurement Accuracy - 5%
Test Duration - 2s nominal
Pass Value - 2 MW
Differential Leakage
Test Voltage - 120V ± 10/%
Load Current - 10A maximum
Test Duration - 30s maximum
Measurement Accuracy - 10%
Pass Value - Class I 3.5mA
Class II 0.25mA
IEC Lead Polarity Test
Test Voltage - 7V nominal
Test Duration - 2s nominal
Test - Live/Neutral checks for o/c, s/c and crossed
Power Socket Test
Input Voltage Range - 120V ± 10/%, 50/60Hz
Voltage Indication - Line Potential Phase to Ground
Line Potential Phase to Neutral
Line Potential Neutral to Ground